Number of changes

Trigger an alarm when a tag changes too often (or too rarely) over a period.

A number of changes condition (also called a frequency condition) watches how often a tag changes over a window of time, rather than its value. Use it to catch equipment that’s cycling too often — a pump short-cycling, a valve hunting — or, the other way round, something that should be changing but isn’t.

Settings

SettingWhat it does
Source tagThe tag whose changes are counted.
OperatorHow the count is compared: equal to, greater than, or less than.
Number of changesThe count to compare against.
PeriodThe length of the window the changes are counted over, with its time unit.

How it triggers

THMI counts how many times the source tag changes within each period, and applies the operator to that count. For example, greater than 10 changes per 1 hour alarms when a pump starts and stops more than ten times in an hour; less than 1 change per 1 day alarms when a value that should move hasn’t moved all day.